Single-end service assembled chambers KSO-366, 393.
Purpose.
KSO-366,393 are used to work in electric plants with supply voltage 6 and 10 kV and three-phase current with current frequency 50 and 60 Hz and voltage 6 (10) kV for systems insulated or grounded neutral point by arcing ground suppressor.
Chambers are different by schemes and equipments of primary and secondary circuits.
Specifications.
|
Parameter name |
Parameter value |
|
Nominal voltage, kV |
6; 10 |
|
Maximum operation voltage (linear), kV |
7.2; 12 |
|
Nominal current of the main circuits, A |
400; 630 |
|
Nominal operational current*, A |
20; 31.5; 40; 50; 80; 100; 160 |
|
Nominal breaking current of the load-break switch at cos ?0.7, А |
630 |
|
Maximum breaking current of the load-break switch at cos ?0.7, А |
800 |
|
Short-time thermal current capacity during 1 s, kA |
10 |
|
Nominal short-time electrodynamic current of the main circuits, kA |
25 |
|
Scaled parameters of the making current, kA: - highest peak - initial vertical value of the periodic component |
2.5 1.0 |
|
Nominal lighting circuits voltage, V |
42 |
|
Insulation (State Standard 1515.1) |
normal |
|
Static force on the handle of the manual drive by operating with the main and earthing knives should not be more than, kgf |
25 |
Operating conditions:
Ambient air temperature - from -25 to 400C.
Relative humidity at 200C - not more than 80%.
Height above sea level - not more than 1000 m.
Non-explosive environment free from aggressive gases and vapours in concentrations that damage metal and insulation.
Operating conditions group with regard to the impact of the environmental mechanical effects - M1 (State Standard 17516.1).
The chambers are made for indoor installation in the electric rooms.
Advantages.
The following high-voltage equipment can be installed in KSO-336, 39:
- load-break switch VNR-10/400-10 UZ, VNA-10/400-10 UZ (with gear PR-17 or PRA-17);
- RVZ or RV disconnectors (with PR-10 drive);
- PTK and PKN or PKE fuses;
- TLK, TOL current transformers;
- NAMI-10, NOM, ZNOL, 3 ZNOLP voltage transformers;
- RVO-6N or RVO-10N switching tube.
The definite types of the equipments and devices are defined in the questionnaire.
Certificates.
State Standard Russia Certificate of Conformity # ROSS RU.PT17.V01604
Issued: 11.09.2008.
Valid before: 10.09.2011.