Modular Integrated Transformer Substations 6(10)/0,4 kV (BKTP).

Purpose.

Modular integrated transformer substations in a concrete casing of outdoor installation with power up to 2500 kVA are used to receive, convert and distribute electricity of three-phase alternating current with current frequency 50 Hz and voltage 6-10/0,4 kV for industrial, public, agricultural, housing objects and also cottage areas and private territories.

Specifications.

Parameter name

Parameter value

Power transformer power, kVA

- sealed oil transformer

- dry-type transformer with cast insulation

160; 250; 400; 630; 1000; 1250

250; 400; 630; 1000; 1250; 1600

Nominal voltage on the HV side, kV

6; 10

Maximum operation voltage on the LV side, kV

7,2; 12

Nominal voltage on the LV side, kV

0,4

Nominal current on the HV side, A

- for network connection

- for transformer connection

400/630/1000

200

Short-time electrodynamic current on the HV side, kA

50

Short-time thermal current on the HV side during 3 sec, kA

20

Insulation level (State Standard 1516.3)

- sealed oil transformer

- dry-type transformer with cast insulation

normal insulation

reduced insulation

Size, mm

2700х5400

Service life period, years

30

Operating conditions:

- height above sea-level - not more than 1000 m;

- ambient air temperature from -45°C to +40°C;

- relative air humidity +20°C – not more than 90%;

- non explosive environment free from aggressive gases or vapours, as well as industrial dust in concentrations that damage metal, protective covers and insulation elements of substation.

Structure.

- high-voltage switchgear;

- power transformer (due to the customer’s order);

- low-voltage switchgear;

- busbars provided by the modular integrated transformer substation construction.

Advantages.

· LLC SPA Sibelectroshield works out projects of modular integrated transformer substations for each costumer;

· High reliability of electrical equipment and absolute safety in use, because of using vacuum and gas-insulated switchers;

· Total operational compatibility, commissioning in 4-5 days after installation;

· Simplicity of constructions and convenience in installation work;

· Possibility to use different types of Russian or import power transformers;

· Possibility to work out an individual project for each object;

· Possibility to use different types of exterior trim, object’s color, working out the designing-projects;

· Molded case of modular integrated transformer substations, seismic resistance up to intensity 9 on the MSK-64 scale;

· Maximal operational compatibility of substations helps to shorten the installation period and the period of commissioning modular integrated transformer substations. According to the electrical schematic diagram which was chosen by the costumer the installation works of electrical equipment are done in plant conditions inside the substation, then the ready-mounted modular integrated transformer substations are delivered to the installation areas.

Sizes.

Possible design of modular integrated transformer substations.

Variant 1

Modular integrated transformer substations -100…1250 (1600)-6 (10)/0,4-U1

Equipment specification

#

Name

Electric scheme

1

Power transformer oil-filled waterproof transformer-100-1250 (1600*)/6(10)/0,4

2

Complete distribution device, 6(10) kV:

- (single-end service assembled chambers-307);

- (RM6, SafeRing)

Example 1, page 17

Example 2, page 17

3

Complete distribution device, 0,4 kV

(low-voltage switch gear cabinet, circuit breaker panel-70)

4

Auxiliaries board

5

Convector 2000 kilowatt NOIROT SPOT E-2

6

Fire-detecting device “VERS-PK”

Electrical schematic diagram.

2modular integrated transformer substation-100…1250 (1600)-6 (10)/0,4-U1 with a separate user’s part

Electrical schematic diagram.

2modular integrated transformer substation-100…1250 (1600)-6 (10)/0,4-U1

Equipment specification

#

Name

Electric scheme

1

Power transformer oil-filled waterproof transformer-100-1250 (1600*)/6(10)/0,4

2

Complete distribution device, 6(10) kV:

- (single-end service assembled chambers-307);

- (RM6, SafeRing)

Example 1, page 21

Example 2, page 21

3

Complete distribution device, 0,4 kV

(low-voltage switch gear cabinet, circuit breaker panel-70)

4

Auxiliaries board

5

Convector 2000 kilowatt NOIROT SPOT E-2

6

Fire-detecting device “VERS-PK”

Electrical schematic diagram

2modular integrated transformer substation-100…1250 (1600)-6 (10)/0,4-U1

Equipment specification

#

Name

Electric scheme

1

Power transformer oil-filled waterproof transformer-100-1250 (1600*)/6(10)/0,4

2

Complete distribution device, 6(10) kV:

- (single-end service assembled chambers-307);

- (RM6, SafeRing)

Example 1, page 23

Example 2, page 23

3

Complete distribution device, 0,4 kV

(low-voltage switch gear cabinet, circuit breaker panel-70)

4

Auxiliaries board

5

Convector 2000 kilowatt NOIROT SPOT E-2

6

Fire-detecting device “VERS-PK”


Certificates.

State Standard Russia Certificate of Conformity # ROSS RU.AV28.V00827.

Issued: 04.05.2009.

Valid before: 03.05.2012.


+7 (3812) 22-64-69